Module no:2703172 LabelId:2703172 Operator:Phoenix
17:11:51, Donnerstag, 28. Juni 2001
G 5/...-EX
(IEC)
rigid
[mm ] solid
2
flexible
stranded AWG
I
U
[A]
[V]
IEC 60 947-7-1
0.2-4
0.2-4
24-12
32
500
EN 50 019 *
0.2-4
0.2-4
–
21
275
* Certificate no.: BAS Ex 89C3087U
H
BASEEFA
Description
Order No.
Pcs.
Pkt.
3 G 5/3-EX
27 03 17 2
50
4 G 5/4-EX
27 03 18 5
50
6 G 5/6-EX
27 03 19 8
50
12 G 5/12-EX
27 03 20 8
50
No. of positions Type
Equipment terminal block,
for direct mounting
Accessories
(1) Marker pin, plastic
unprinted: for labeling with marker
pen
BN WH:… (see info)
printed: with 1, 2 or 3 characters,
white
BNB WH…1)
100
14 01 41 7
100
Technical data
see description drawing
Dimensions
Technical data in accordance with IEC 60 947-7-1
Maximum load current / cross section
Rated surge voltage / contamination class
Surge voltage category / insulation
material group
2
[A] / [mm ]
32 / 4
[kV] / –
6/3
–/–
III / I
Connection capacity
Stranded with ferrule without / with plastic
sleeve
2
[mm ]
0.25 - 4 / 0.25 - 2.5
Multi-conductor connection (2 conductors with same
cross section)
2
0.2 - 1.5 / 0.2 - 1.5
2
0.25 - 1.5
[mm ]
2
0.5 - 1.0
[mm]
8
Solid / stranded
[mm ]
Stranded with ferrule without plastic sleeve
[mm ]
Stranded with TWIN ferrule with plastic
sleeve
Stripping length
Phoenix Contact Elektronischer Katalog
Page 1 / 2
Module no:2703172 LabelId:2703172 Operator:Phoenix
17:11:51, Donnerstag, 28. Juni 2001
Internal cylindrical gage (IEC 60 947-1:1988)
A3
Thread
M3
[Nm]
Torque
0.6 - 0.8
Insulation material
PA
Inflammability class acc. to UL 94
V2
Temperature indices RTI acc. to UL 746 B / Ti acc. to IEC
60 216-1
Installation temperature range /
temperature class
[°C] / –
125 / 100
-25...+80 / T6
1
) Required marking is to be specified.
Technical Data
Type
a
b
G 5/3
31
11
G 5/4
38
18
G 5/6
52
32
G 5/12
92
72.5
Important Ex note:
All clamping screws must be tightened.
Dimensional drawing
Phoenix Contact Elektronischer Katalog
Page 2 / 2
很抱歉,暂时无法提供与“G 5/ 4-EX”相匹配的价格&库存,您可以联系我们找货